Back
 JEP  Vol.6 No.8 , August 2015
The Choice of Appropriate Scenario in Order to Reduce the Effect of Thermal Pollution at the Damietta Branch Caused by Cooling Water Discharged from Kafr-Al-Batek Power Station
Abstract: The main purpose of this research effort was to investigate and reduce the volume of thermal polluted cooling water from returning to the Kafr-Al-Batek power station. Traditional cooling systems, such as cooling towers or ponds can be very challenging with regards to implementation in developing countries; mainly due to the lack of financial capacity. This research focused on low-cost simulation solutions that could improve thermal outcomes. Comparisons were performed between three different scenarios to decrease the elevated temperature of the discharged water (43 °C) released by the Kafr-Al-Batek power station on the Damietta branch. The different scenarios were simulated by using Star CCM+ software. The base scenario examined the discharge angle of an existing outlet. The second scenario examined a new outlet downstream from the existing outlet. The third scenario increased the width of the existing outlet in order to reduce flow velocity. A comparative analysis is provided between the aforementioned solutions to identify the most suitable and cost-effective alternative. Simulation results show that changing the discharge angle from 90° to 135° is the most effective solution. Applying this solution has the potential to decrease the water temperature at the inlet by 7 degrees Celsius (from 32 °C to 25 °C).
Cite this paper: Mostafa, S. , Mostafa, M. and Kirby, J. (2015) The Choice of Appropriate Scenario in Order to Reduce the Effect of Thermal Pollution at the Damietta Branch Caused by Cooling Water Discharged from Kafr-Al-Batek Power Station. Journal of Environmental Protection, 6, 857-866. doi: 10.4236/jep.2015.68078.
References

[1]   Ager, D., David, M. and Paul, P. (2008) Bay Shore Power Plant Cooling Water Intake Structure Information and I&E Sampling Data. Environment and Aquatic Management Services, Algonquin.

[2]   Nathanson, J.A. (2013) E-Study guide for: Basic Environmental Technology: Water Supply, Waste Management and Pollution Control. 9th Edition, Just The Facts I0I Textbook Key Facts, Content Technologies Inc., Bellevue.

[3]   Agarwal, R.K. and Sangal, V.K. (2010) Environment and Ecology. Krishna Prakashan Media (P) Ltd., Meerut.

[4]   Mostafa, M. (2014) Modeling of Pollutant Transport in the Nile Delta Egypt. Ph.D. Dissertation. University of Alabama at Birmingham, Birmingham.

[5]   Nordell, B. (2003) Thermal Pollution Causes Global Warming. Global and Planetary Change, 38, 305-312.
http://dx.doi.org/10.1016/S0921-8181(03)00113-9

[6]   Walkuska, G. and Agnieszka, W. (2010) Influence of Discharged Heated Water on Aquatic Ecosystem Fauna. Faculty of Veterinary Medicine in Lublin, University of Life Sciences in Lublin, Lublin, Poland.
http://www.pjoes.com/pdf/19.3/547-552.pdf

[7]   Andrew, D.E., Lenore, S.C., Eugene, W.R. and Arnold, E.G. (2005) Standard Methods for the Examination of Water and Wastewater. 21st Edition, American Public Health Association, Washington DC.

[8]   American Public Health Association (APHA) (2005) Standard Methods for the Examination of Water and Wastewater. Washington DC.

[9]   Clesceri, L.S., Greenberg, A.E. and Trussell, R.R. (1989) Standard Methods for the Examination of Water and Wastewater. 17th Edition, American Public Health Association, Washington DC.

[10]   Department of Defense (2011) High Performance Computing Modernization Program. Users Group Conference, Portland.

[11]   Coker, A.K. (2001) Modeling of Chemical Kinetics and Reactor Design. Gulf publishing Company, Houston.

[12]   Haren, S.W. (2011) Testing DNS Capability of Open FOAM and STAR-CCM+. Master Thesis, Delft University of Technology, Delft.

[13]   Bertholds, A. (2013) Efficient Modeling of the Regenerative Heat Transfer in a Rotary Kiln. Project in Computational Science: Report, Uppsala University, Uppsala.

 
 
Top