An Efficient Method for Earth Resistance Reduction Using the Dead Sea Water
Abstract: To protect humans, devices and maintain high reliability of electrical equipments, efficient earthing system has to be provided for residential and commercial buildings. The use of chemical elements around the electrode of earthing systems reduces the earth resistance which improves the efficiency of these systems. However, the use of these elements can’t achieve very small earth resistance especially in the case of dry clay. In addition, they are expensive and not available all the time. This paper presents a method that treats the soil with adding the Dead Sea water instead of the chemical elements to further reduce the earth resistance and to avoid the expenses of these elements. In our approach, the Dead Sea water is added to a hole around the electrode with a distance not exceeding 10 cm to avoid the corrosion layer on the electrode. Practical measurements are demonstrated to show the efficiency of the proposed approach.
Cite this paper: El-Tous, Y. and Alkhawaldeh, S. (2014) An Efficient Method for Earth Resistance Reduction Using the Dead Sea Water. Energy and Power Engineering, 6, 47-53. doi: 10.4236/epe.2014.64006.
References

[1]   Hammuda1, A., Nouri, H. and Al-Ayoubi, M. (2011) An Investigation into Substation Grounding and Its Implementation on Gaza Substation. Energy and Power Engineering, 3, 593-599.

[2]   Kinsler, M. (1998) A Damage Mechanism: Lightning-Initiated Fault-Current Area to Communication Cables Buried Beneath Overhead Electric Power Lines. IEEE Industrial and Commercial Power Systems Technical Conference, 109-118.

[3]   Na, J., Kang, H., Kim, Y., Chang, K., Hwang, Y. and Ko, T. (2011) Experimental Study on the Lightning Impulse Dielectric Characteristics of Sub-Cooled Liquid Nitrogen for a High Voltage Superconducting Fault Current Limiter. IEEE Transactions on Applied Superconductivity, 21, 1336-1339. http://dx.doi.org/10.1109/TASC.2011.2105456

[4]   Dusang, L.V. (2008) A Ground Fault Protection Method for Ungrounded Systems. IEEE Electric Power Conference EPEC, 1-6.

[5]   Ferrell, B. and Ostdyk, R. (2010) Modeling and Performance Considerations for Automated Fault Isolation in Complex Systems. IEEE Aerospace Conference, 1-8.

[6]   Kamel, R., Chaouachi, A. and Nagasaka, K. (2011) Comparison the Performances of Three Earthing Systems for Micro-Grid Protection during the Grid Connected Mode. Smart Grid and Renewable Energy, 2, 206-215.
http://dx.doi.org/10.4236/sgre.2011.23024

[7]   Colominas, I., Gómez-Calvino, J., Navarrina, F. and Casteleiro, M. (2001) Computer analysis of Earthing Systems in Horizontally or Vertically Layered Soils. Electric Power Systems Research, 59, 149-156.
http://dx.doi.org/10.1016/S0378-7796(01)00148-1

[8]   Shalash, N., Haidar, A. and Abdul Sattar, K. (2012) Grounding Locations Assessment of Practical Power System. Energy and Power Engineering, 4, 19-27. http://dx.doi.org/10.4236/epe.2012.41003

[9]   Roberts, J. and Aituve, J. (2001) Review of Ground Fault Protection Methods for Grounded, Ungrounded, and Compensated Distribution Systems, SEL.

[10]   Hanninen, S. (2001) Single Phase Earth Faults in High Impedance Grounded Networks Characteristics, Indication and Location. Valtion Teknillinen Tutkimuskeskus Technical Research Centre of Finland, Espoo.

[11]   Kojovic, L.A., Day, T.R. and Chu, H.H. (2003) Effectiveness of Restricted Ground Fault Protection with Different Relay Types. Power Engineering Society General Meeting, IEEE, 13-17 July 2003, 1-6.

[12]   Jinxi, M. and Dawalibi, F.P. (2006) Grounding Analysis of a Large Electric Power Station. IEEE International Conference on Power System Technology, Chongqing, 22-26 October 2006, 1-6.

[13]   Jacob, D. and Nithiyananthan, K. (2008) Effective Methods for Power Systems Grounding. WSEAS Transactions on Business and Economics, 5, 151-160.

 
 
Top