Back
 EPE  Vol.12 No.6 , June 2020
Computer Simulation of an Ammonia-Water Absorption Cycle for Refrigeration: Using a Distillation Tower to Replace the Generator
Abstract:
By using a distillation tower as the regenerator, the coefficient of performance (COP) of the ammonia-water absorption refrigeration cycle is calculated in this work. Two types of distillation towers, namely an equilibrium-stage tower with a total condenser and a packed-bed tower with a partial condenser, are used in the cycle. From the simulation results, it is found that both types of distillation towers can successfully increase the COP of the cycle due to increased ammonia concentration in the vapor phase of the ammonia-water refrigerant. It was also found that the tower equipped with a partial condenser provides higher COP than that of the tower equipped with a total condenser. The value of COP can be further increased when the generator is replaced by the packed-bed tower in this water-ammonia absorption cycle. The effects of the mass flow rate ratio of NH3/H2O, stage number, reflux ratio and energy duty of the tower on the COP of the cycle are also studied in the present paper.
Cite this paper: Chang, Y. , Wu, L. , Wu, C. and Jang, L. (2020) Computer Simulation of an Ammonia-Water Absorption Cycle for Refrigeration: Using a Distillation Tower to Replace the Generator. Energy and Power Engineering, 12, 237-256. doi: 10.4236/epe.2020.126015.
References

[1]   Arora, C.P. (2009) Refrigeration and Air Conditioning. Third Edition, The McGraw Hill Education Pvt. Ltd., New York, 437-442.

[2]   Shukla, A., Mishara, A., Shukla, D. and Cauhan, K. (2015) C.O.P Derivation and Thermondymanic Calculation of Ammonia-Water Vapor Absorption Refrigeration System. International Journal of Mechanical Engineering and Technology, 6, 72-81.

[3]   Rossa, J.A. and Bazzo, E. (2009) Thermodynamic Modeling of an Ammonia-Water Absorption System Associated with a Microturbine. International Journal of Thermodynamics, 12, 38-43.

[4]   Kong, T.D.F., Liu, J.H., Zhang, L., He, H. and Fang, Z.Y. (2010) Thermodynamic and Experimental Analysis of an Ammonia-Water Absorption Chiller. Energy and Power Engineering, 2, 298-305.
https://doi.org/10.4236/epe.2010.24042

[5]   Hong, D., Tang, L., He, Y. and Chen, G. (2010) A Novel Absorption Refrigeration Cycle. Applied Thermal Engineering, 30, 2045-2050.
https://doi.org/10.1016/j.applthermaleng.2010.05.010

[6]   Ouadha, A. and EI-Gotni, Y. (2013) Integration of an Ammonia-Water Absorption Refrigeration System with a Marine Diesel Engine: A Thermodynamic Study. Procedia Computer Science, 19, 754-761.
https://doi.org/10.1016/j.procs.2013.06.099

[7]   Oza, V.H. and Bhatt, N.M. (2018) Thermodynamic Analysis of Ammonia-Water Absorption Refrigeration System with Ejector. International Journal of Mechanics and Solids, 13, 95-110.

[8]   Kaewpraduba, S., Sanguandueana, P., Katesuwana, W., Chimresa, N., Punyasukhanandab, P., Asirvathamc, L.G., Mahiand, O., Dalkilice, A.S. and Wongwisesa, S. (2018) Absorption Refrigeration System Using Engine Exhaust Gas as an Energy Source. Case Studies in Thermal Engineering, 12, 797-804.
https://doi.org/10.1016/j.csite.2018.10.003

[9]   Wijaksana, H., Winaya, I.N.S., Sucipta, M. and Ghurri, A. (2019) The Investigation of Influence Ammonia Concentration Variations to the Performance of a Pump Less Ammonia-Water Absorption Refrigeration System with Water Flooding Evaporator. AIP Conference Proceedings, 2062, Article ID: 020053.
https://doi.org/10.1063/1.5086600

[10]   Babu, M.S., Prasad, L.D., Prasad K.S.D., Vikas, M. and Kishore, P.S. (2019) Performance of Ammonia-Water Vapor Absorption Refrigeration System. Journal of Emer- ging Technologies and Innovative Research, 6, 207-214.

[11]   Kaushik, S.C. and Bhardwaj, S.C. (1982) Theoretical Analysis of Ammonia-Water Absorption Cycles for Refrigeration and Space Conditioning Systems. Energy Research, 6, 205-225.
https://doi.org/10.1002/er.4440060302

[12]   Clerx, M. and Trezek, G.J. (1987) Performance of an Aqua-Ammonia Absorption Solar Refrigerator at Sub-Freezing Evaporator Conditions. Solar Energy, 39, 379-389.
https://doi.org/10.1016/S0038-092X(87)80056-7

[13]   Best, R. and Hernandez, J. (1991) Experimental Studies on the Operating Characteristics of an Ammonia-Water Absorption System for Solar Cooling. Applied Energy, 69, 153-160.

[14]   Raghuvanshi, S. and Maheshwari, G. (2011) Analysis of Ammonia-Water (NH3- H2O) Vapor Absorption Refrigeration System Based on First Law of Thermodynamics. International Journal of Scientific & Engineering Research, 2, 39-45.

[15]   Cai, W.H., Sen, M. and Paolucci, S. (2012) Dynamic Simulation of an Ammonia-Water Absorption Refrigeration System. Industrial & Engineering Chemistry Research, 51, 2070-2076.
https://doi.org/10.1021/ie200673f

[16]   Habibzadeh, A., Jafarmadar, S., Rashidi, M.M., Rezaei, S.S. and Aghagoli, A. (2017) Energy and Exergy Analysis of an Ejector-Absorption Refrigeration Cycle with Using NH3-H2O as the Working Fluids. Journal of Environmental Friendly Materials, 1, 45-54.

[17]   (2017) Aspen plus Version-10.0. Aspen Technology Inc., Houston.

[18]   Darwish, N.A., Al-Hashimi, S.H. and Al-Mansoori, A.S. (2008) Performance Analysis and Evaluation of a Commercial Absorption-Refrigeration Water-Ammonia (ARWA) System. International Journal of Refrigeration, 31, 1214-1223.
https://doi.org/10.1016/j.ijrefrig.2008.02.005

[19]   Chang, Y.I., Wu, L.C. and Wu, C.C. (2000) The Advantage of Using a Distillation Tower in an Ammonia-Water Absorption Cycle for Refrigeration. Chinese Journal of Chemical Engineering, 31, 193-197.

 
 
Top